IFC-640
Intelligent Addressable
Fire Alarm System
JCI-6856:A
IFC-640 shown in CAB-4 with
JNCA 640-character display
General
As a stand-alone small-to-large system, or as a large network,
the IFC-640 meets virtually every application requirement.
Designed with modularity and for ease of system planning, the
IFC-640 can be configured with just a few devices for small
building applications, or for a large campus or high-rise applica-
tion. Simply add additional peripheral equipment to suit the
application.
Features
One, expandable to two, isolated intelligent Signaling Line
Circuit (SLC) Style 4, 6 or 7.
Up to 159 detectors (any mix of ion, photo, thermal, or multi-
sensor) and 159 modules (N.O. manual stations, two-wire
smoke, notification, or relay) per SLC. 318 devices per loop/
636 per FACP or network node.
Standard 80-character display, 640-character large display,
or display-less (a node on a network).
Network option – 103 nodes supported (IFC-640, JNCA Net-
work Annunciator, or IFW Network Control Station).
6.0 amp switch mode power supply with four Class A/B built-
in Notification Appliance Circuits (NAC). Selectable System
Sensor strobe synchronization.
Built-in Alarm, Trouble, and Supervisory relays.
Up to 64 output circuits per FACP or network node; circuits
configurable online.
Autoprogramming and Walk Test reports.
Optional universal 636-point DACT.
80-character remote annunciators (up to 32).
EIA-485 annunciators, including custom graphics.
Printer interface (80-column and 40-column printers).
History file with 800-event capacity in nonvolatile memory,
plus separate 200-event alarm-only file.
Alarm Verification selection per point, with tally.
Autoprogramming and Walk Test reports.
Positive Alarm Sequence (PAS) Presignal.
Silence inhibit and Auto Silence timer options.
March time / temporal / California two-stage coding / strobe
synchronization.
Field-programmable on panel or on PC
Full QWERTY keypad.
Charger for up to 90 hours of standby power.
Non-alarm points for lower priority functions.
Remote ACK/Signal Silence/System Reset/Drill via monitor
modules.
Automatic time control functions, with holiday exceptions.
Surface Mount Technology (SMT) electronics.
Extensive, built-in transient protection.
Powerful Boolean logic equations.
JNCA 640-CHARACTER DISPLAY FEATURES:
Backlit, 640-character display.
Supports SCS Series smoke control system in both HVAC or
FSCS modes .
Printer and CRT EIA-232 ports.
EIA-485 annunciator and terminal mode ports.
Alarm, Trouble, Supervisory, and Security relays.
FLASHSCAN® INTELLIGENT FEATURES:
Poll 318 devices in less than two seconds.
Activate up to 159 outputs in less than five seconds.
Multicolor LEDs blink device address during Walk Test.
Fully digital, high-precision protocol (U.S. Patent 5,539,389).
Manual sensitivity adjustment — nine levels.
Pre-alarm AWACS — nine levels.
Day/Night automatic sensitivity adjustment.
Sensitivity windows:
–Ion 0.5 to 2.5%/foot obscuration.
–Photo 0.5 to 2.35%/foot obscuration.
– Laser (VIEW®) – 0.02 to 2.0%/foot obscuration.
–Acclimate 0.5 to 4.0%/foot obscuration.
–HARSH 0.5 to 2.35%/foot obscuration.
Drift compensation (U.S. Patent 5,764,142).
Degraded mode — in the unlikely event that the JCPU-640
microprocessor fails, FlashScan® detectors revert to
degraded operation and can activate the JCPU-640 NAC cir-
cuits and alarm relay. Each of the four built-in panel circuits
includes a Disable/Enable switch for this feature.
Page view 0
1 2 3 4 5 6 7 8 9

Summary of Contents

Page 1 - Fire Alarm System

JCI-6856:A • 12/01/06 — Page 1 of 9IFC-640Intelligent Addressable Fire Alarm SystemJCI-6856:AIFC-640 shown in CAB-4 with JNCA 640-character displayGen

Page 2 -

Page 2 of 9 — JCI-6856:A • 12/01/06 • Multi-detector algorithm involves nearby detectors in alarmdecision (U.S. Patent 5,627,515).• Automatic

Page 3

JCI-6856:A • 12/01/06 — Page 3 of 9FlashScan®Exclusive World-Leading Detector Pro-tocolAt the heart of the IFC-640 is a set of detection devices andde

Page 4 - Network Diagram

Page 4 of 9 — JCI-6856:A • 12/01/06 TOP, LEFT to RIGHT: J8 Zone Code Input; TB7 DC Power (24 VDC power-limited, both resettable and non-resettabl

Page 5 - Configuration Guidelines

JCI-6856:A • 12/01/06 — Page 5 of 9Placement of Equipment in Chassis and CabinetThe following guidelines outline the IFC-640’s flexible systemdesign.R

Page 6 - System Modules

Page 6 of 9 — JCI-6856:A • 12/01/06CHS-M2: Mounting chassis for JCPU-640. One required foreach CPU-640/-640E.DP-DISP: Dress panel for top row in ca

Page 7 - OTHER OPTIONS

JCI-6856:A • 12/01/06 — Page 7 of 9LDM: Lamp Driver Modules LDM-32, LDM-E32, and LDM-R32.See LDM technical bulletin.ACM-8R: Remote Relay Module wit

Page 8

Page 8 of 9 — JCI-6856:A • 12/01/06TM-4: Transmitter Module. Includes three reverse-polarity cir-cuits and one municipal box circuit. Mounts in panel

Page 9 - SYSTEM SPECIFICATIONS

System Capacity• Intelligent Signaling Line Circuits ....1 expandable to 2• Intelligent detectors ...........1

Comments to this Manuals

No comments