Johnson-controls ACPU024 THRU 060 User Manual Page 11

  • Download
  • Add to my manuals
  • Print
  • Page
    / 32
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 10
279815-PTG-D-0408
Johnson Controls Unitary Products 11
115°F 125°F
1000
77 36.0 3.6 17.9 14.4 10.9 - - - 32.6 3.9 16.6 13.2 9.9 - - -
72 32.6 3.5 23.2 19.7 16.2 12.8 - - 29.5 3.8 21.7 18.4 15.1 11.7 - -
67 29.3 3.4 28.6 25.1 21.6 18.1 14.6 - 26.4 3.6 26.4 23.5 20.2 16.9 13.6 -
62 26.7 3.3 26.7 26.7 26.9 23.4 20.0 16.5 24.1 3.5 24.1 24.1 24.1 22.4 19.1 15.7
57 26.5 3.3 26.5 26.5 26.4 23.0 19.5 16.0 24.2 3.6 24.2 24.2 24.2 20.9 17.6 14.2
1125
77 36.7 3.7 23.4 16.2 11.7 - - - 33.2 4.0 23.8 15.3 10.8 - - -
72 33.3 3.6 26.5 22.0 17.5 13.0 - - 30.0 3.9 25.5 20.9 16.4 11.9 - -
67 29.9 3.5 29.5 27.8 23.3 18.8 14.3 - 26.8 3.7 26.8 26.6 22.1 17.5 13.0 -
62 27.2 3.4 27.2 27.2 27.4 22.9 18.4 13.9 24.5 3.6 24.5 24.5 24.5 20.9 16.3 11.8
57 27.1 3.4 27.1 27.1 27.0 22.5 18.1 13.6 24.6 3.7 24.6 24.6 24.6 20.3 15.6 11.1
1250
77 37.4 3.8 29.0 18.1 12.6 - - - 33.7 4.1 31.1 17.4 11.7 - - -
72 34.0 3.7 29.8 24.3 18.8 13.3 - - 30.5 4.0 29.2 23.5 17.8 12.1 - -
67 30.5 3.6 30.5 30.5 25.0 19.5 14.0 - 27.3 3.8 27.3 27.3 23.9 18.2 12.5 -
62 27.8 3.5 27.8 27.8 27.8 22.3 16.8 11.3 24.9 3.8 24.9 24.9 24.9 19.4 13.5 7.8
57 27.6 3.5 27.6 27.6 27.6 22.1 16.6 11.1 25.1 3.8 25.1 25.1 25.1 19.6 13.7 8.0
1375
72 34.3 3.8 31.1 25.3 19.4 13.6 - - 30.8 4.0 30.1 24.2 18.3 12.3 - -
67 30.8 3.7 30.8 30.8 25.8 20.0 14.1 - 27.6 3.9 27.6 27.6 24.5 18.5 12.6 -
62 28.0 3.6 28.0 28.0 28.0 22.2 16.3 10.5 25.2 3.8 25.2 25.2 25.2 19.3 13.3 7.3
57 27.9 3.6 27.9 27.9 27.9 22.0 16.2 10.3 25.3 3.8 25.3 25.3 25.3 19.5 13.4 7.5
1500
72 34.6 3.8 32.5 26.3 20.1 13.8 - - 31.1 4.1 31.1 24.9 18.7 12.5 - -
67 31.1 3.7 31.1 31.1 26.7 20.5 14.2 - 27.8 3.9 27.8 27.8 25.1 18.9 12.7 -
62 28.3 3.6 28.3 28.3 28.3 22.1 15.9 9.6 25.4 3.8 25.4 25.4 25.4 19.2 13.0 6.8
57 28.2 3.6 28.2 28.2 28.2 21.9 15.7 9.5 25.5 3.9 25.5 25.5 25.5 19.4 13.2 7.0
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
TABLE 5: COOLING CAPACITIES - 3 TON (ACP036) (CONTINUED)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65