364861-UIM-B-0708EFFICIENCYRATINGCERTIFIEDISO 9001Certified QualityManagement SystemRESIDENTIAL GAS FURNACE MODELSTG9S*MP, GG9S*MP(95.5% AFUE Single S
364861-UIM-B-070810 Johnson Controls Unitary ProductsThe furnace must be isolated from the gas supply piping system byclosing its individual external
364861-UIM-B-0708Johnson Controls Unitary Products 11Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test proc
364861-UIM-B-070812 Johnson Controls Unitary ProductsFor additional connection diagrams for all UPG equipment refer to “Low Voltage System Wiring” doc
364861-UIM-B-0708Johnson Controls Unitary Products 13 FIGURE 19: Thermostat Chart - Single Stage HP with Single Stage PSC FurnacesHP 2C Single Stage
364861-UIM-B-070814 Johnson Controls Unitary ProductsACCESSORY CONNECTIONSThe furnace control will allow power-switching control of various acces-sori
364861-UIM-B-0708Johnson Controls Unitary Products 15Single-Wire Twinning OperationHeating - On a call for heat (W signal) from the wall thermostat, b
364861-UIM-B-070816 Johnson Controls Unitary ProductsSECTION VII: CONDENSATE PIPING AND FURNACE VENTING CONFIGURATIONCONDENSATE DRAIN LOCATIONAs shipp
364861-UIM-B-0708Johnson Controls Unitary Products 17 FIGURE 23: Upflow ConfigurationINDUCER ROTATED FORLEFT SIDE VENTING(As required for 130K model)
364861-UIM-B-070818 Johnson Controls Unitary Products FIGURE 24: Downflow ConfigurationAIRFLOWAIRFLOWMove raingutter hoseto this positionDOWNFLOW - I
364861-UIM-B-0708Johnson Controls Unitary Products 19 FIGURE 25: Horizontal Left ConfigurationHORIZONTAL - LEFTINDUCER ROTATEDHORIZONTAL - LEFTINDUCE
364861-UIM-B-07082 Johnson Controls Unitary ProductsSPECIFIC SAFETY RULES AND PRECAUTIONS1. Only Natural gas or Propane (LP) gas are approved for use
364861-UIM-B-070820 Johnson Controls Unitary Products FIGURE 26: Horizontal Right ConfigurationAIRFLOWHORIZONTAL - RIGHTINDUCER ROTATEDHORIZONTAL - R
364861-UIM-B-0708Johnson Controls Unitary Products 21SECTION VIII: COMBUSTION AIR AND VENT SYSTEMCOMBUSTION AIR AND VENT SAFETYThis Category IV, dual
364861-UIM-B-070822 Johnson Controls Unitary ProductsExample:An 80,000 BTUH furnace requires 32 feet of pipe and four 90º elbows.Using 2" pipe an
364861-UIM-B-0708Johnson Controls Unitary Products 23VENT CLEARANCES† A vent shall not terminate directly above a sidewalk or paved driveway that is l
364861-UIM-B-070824 Johnson Controls Unitary ProductsVENT SYSTEMThis furnace is certified to be installed with one of two possible ventconfigurations.
364861-UIM-B-0708Johnson Controls Unitary Products 25COMBUSTION AIR SUPPLYAll installations must comply with Section 5.3, Air for Combustion andVentil
364861-UIM-B-070826 Johnson Controls Unitary ProductsAir Supply Openings and Ducts1. An opening may be used in lieu of a duct to provide to provide th
364861-UIM-B-0708Johnson Controls Unitary Products 27Ventilated Combustion AirThe ventilated attic space or a crawl space from which the combustionair
364861-UIM-B-070828 Johnson Controls Unitary ProductsSECTION IX: START-UP AND ADJUSTMENTSThe initial start-up of the furnace requires the following ad
364861-UIM-B-0708Johnson Controls Unitary Products 29Table 14: Gas Rate (CU FT/HR) at Full InputSeconds For 1 RevolutionSize of Test DialSeconds For 1
364861-UIM-B-0708Johnson Controls Unitary Products 3CODES AND STANDARDSFollow all national, local codes and standards in addition to this installa-tio
364861-UIM-B-070830 Johnson Controls Unitary ProductsADJUSTMENT OF MANIFOLD GAS PRESSURE & INPUT RATEInlet and manifold gas pressure may be measur
364861-UIM-B-0708Johnson Controls Unitary Products 31ADJUSTMENT OF TEMPERATURE RISEAfter about 5 minutes of operation, determine the furnace temperatu
364861-UIM-B-070832 Johnson Controls Unitary ProductsLIMIT CONTROLSThere is a high temperature limit control located on the furnace vesti-bule panel n
364861-UIM-B-0708Johnson Controls Unitary Products 333 RED FLASHES: This indicates the normally open pressure switchcontact did not close after the in
364861-UIM-B-070834 Johnson Controls Unitary ProductsSECTION XI: REPLACEMENT PARTS LISTDESCRIPTIONMOTORMOTOR, DIRECT DRIVE BLOWERBLOWER, COMBUSTIONELE
364861-UIM-B-0708Johnson Controls Unitary Products 35SECTION XII: WIRING DIAGRAM FIGURE 42: Wiring Diagram
Subject to change without notice. Printed in U.S.A. 364861-UIM-B-0708Copyright © 2008 by Johnson Controls, Inc. All rights reserved. Supersedes: 36486
NOTES:1. Refer to the condensate management and drain hoseplumbing for different configurations in this document. Nohose clamps are needed for the con
Furnace is multi-position and may be installed in any of the configurations shown.Ensure that all PVC venting has at least 1/4” per foot slope towards
364861-UIM-B-07084 Johnson Controls Unitary ProductsFURNACE LOCATION AND CLEARANCESThe furnace shall be located using the following guidelines:1. Wher
364861-UIM-B-0708Johnson Controls Unitary Products 5On all installations without a coil, a removable access panel is recom-mended in the outlet duct s
364861-UIM-B-07086 Johnson Controls Unitary ProductsCOIL FLANGE INSTALLATIONThe coils include removable flanges to allow proper fit up with furnacesha
364861-UIM-B-0708Johnson Controls Unitary Products 7DOWNFLOW DUCT CONNECTORSAll downflow installations must use a suitable duct connector approvedby t
364861-UIM-B-07088 Johnson Controls Unitary ProductsSECTION III: FILTERSFILTER INSTALLATIONAll applications require the use of a field installed filte
364861-UIM-B-0708Johnson Controls Unitary Products 9SIDE RETURNLocate the “L” shaped corner locators. These indicate the size of the cut-out to be mad