10 Johnson Controls Unitary Products
TABLE 7: PHYSICAL DATA
MODEL
DNA
018 024 030 036 042 048 060
EVAPORATOR
BLOWER
CENTRIFUGAL BLOWER (Dia. x W. in.) 10 x 8 10 x 8 10 x 8 11 x 10 11 x 10 12 x 11 12 x 11
FAN MOTOR HP (3 Speed) 1/2 1/2 1/2 3/4 3/4 1 1
EVAPORATOR
COIL
ROWS DEEP 2222333
FINS PER INCH 14 13 13 15 13 13 13
FACE AREA (Sq. Ft.) 2.25 3.5 3.5 3.5 3.5 4.5 4.5
CONDENSER
FAN
PROPELLER DIA. (in.) 22222222222222
FAN MOTOR HP 1/4 1/4 1/4 1/4 1/4 1/4 1/4
NOM. CFM TOTAL 1,800 2,200 2,400 2,400 2,400 3,000 3,000
CONDENSER
COIL
ROWS DEEP 1111111
FINS PER INCH 13 13 16 20 20 20 20
FACE AREA (Sq. Ft.) 8.3 8.3 11.7 11.7 11.7 14.8 14.8
CHARGE REFRIGERANT 22 (lbs./oz.) 3 / 2 3 / 16 4 / 12 4 / 3 4 / 9 6 / 0 5 / 4
FILTER
1
FACE AREA (Sq. Ft.) Size (Nominal) 2.6/20x20 2.6/20x20 2.6/20x20 2.6/20x20 2.6/20x20 3.3/20x12 3.3/20x12
FURNACE
SECTION
NATURAL GAS BURNER ORIFICE NO. (Drill Size) 43 43 43 43 43 40 40
PROPANE BURNER ORIFICE NO. (Drill Size) 55 55 55 55 55 53 53
GAS CONNECTION SIZE
1/2
NPTI 1/2 NPTI 1/2 NPTI 1/2 NPTI 1/2 NPTI 1/2 NPTI 1/2 NPTI
COMPRESSOR
TYPE
HERMETICALLY SEALED
(R = RECIPROCATING, S = SCROLL)
RRRRRSS
1.
See FILTERS on page 5.
TABLE 8: ELECTRICAL DATA
MODEL
DNA
POWER
SUPPLY
VOLTAGE
LIMITATIONS
1
COMPRESSOR
COND.
FAN
MOTOR,
FLA
SUPPLY
AIR
BLOWER
MOTOR
FLA
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE,
AMPS
2
MAX.
HACR
BREAKER
SIZE,
AMPS
UNIT
POWER
FACTOR
TRANSFORMER
SIZE (VA)
MIN. MAX. RLA LRA
018 208/230-1-60 187 253 9.0 48.0 1.1 2.2 14.5 20 20 .96 40
024 208/230-1-60 187 253 11.5 60.0 1.1 2.2 17.7 25 25 .96 40
030 208/230-1-60 187 253 14.7 73.0 1.1 2.2 21.7 30 30 .96 40
036 208/230-1-60 187 253 17.3 94.0 1.1 3.5 26.2 35 35 .96 40
042 208/230-1-60 187 253 15.4 86.0 1.1 3.5 23.9 30 30 .96 40
048 208/230-1-60 187 253 24.4 140.0 1.3 7.0 38.8 50 50 .96 40
060 208/230-1-60 187 253 28.9 175.0 1.3 7.0 44.4 60 60 .96 40
1.
Utilization range “A” in accordance with ARI Standard 110.
2.
Dual element, time delay type.